Briton Refrigerant R407c

Briton Refrigerant R407c Gas

Briton Refrigerant R407c

Difluoromethane
Pentafluoroethane
Tetrafluoroethane

Briton Refrigerant R-407C gas is a mixture of hydrofluorocarbons used as a refrigerant. It is a zeotropic blend of difluoromethane (R-32), pentafluoroethane (R-125), and 1,1,1,2-tetrafluoroethane (R-134a). Difluoromethane serves to provide the heat capacity, pentafluoroethane decreases flammability, tetrafluoroethane reduces pressure. R-407C cylinders are colored burnt orange.

It is not recommended to drop R-407C into R-22 systems on top of the existing charge in cases of low refrigerant levels. A licensed professional should be contracted to completely remove the R-22 and as much of the mineral oil as possible. In the case of compressor change-outs, replacement compressors are already manufactured with POE (polyolester) oil and are therefore more compatible with R-407C than returning the recovered R-22. The recovered R-22 can be sent to a facility for disposal.

It is cost effective to replace R-22 with R-407C before there is an emergency. Preventive maintenance programs should include strong suggestions to replace ozone-depleting refrigerants such as R-22 with environmentally friendly refrigerants and it seems that R-407C has become the front runner. There are many millions of tons of R-22 in air conditioning and refrigeration equipment in use today and most of it is destined to end up in the atmosphere in spite of efforts to curtail this probability.

Downloads

Download Briton Refrigerant R407c Gas Material Safety Data Sheet (MSDS).

Product InformationProduct SpecificationMaterial Safety Data Sheet (MSDS)
Download pdfDownload pdfDownload pdf
 

General Information

General Information of Briton Refrigerant R407c (Difluoromethane, Pentafluoroethane, Tetrafluoroethane)

ItemSpecification
ASHRAE #R-407C
ClassHFC
Refrigerant TypeBlend
Typical LubricantPOE
NotesCommercial Refrigeration: Reasonable performance match to R-22 in medium temperature refrigeration. Lower capacity in low temperature refrigeration systems. Air Conditioning and Heat Pumps: Best retrofit alternative to R-22. Close performance match with slightly higher operating pressures.
 
Physical Properties

Physical Properties of Briton Refrigerant R407c (Difluoromethane, Pentafluoroethane, Tetrafluoroethane)

PropertyValue
Chemical NameDifluoromethane, Pentafluoroethane, Tetrafluoroethane
Chemical NotationCH2F, CF3CHF2, CF3CH2F (52% R-134a / 25% R-125 / 23% R-32)
Critical Temperature (°C)86.03
Critical Pressure (bar)46.29
Liquid Density (kg/m³) 0°C1137.5
ANSIASHRAE Standard 36-1992 Safety Group ClassificationA1
Relative Molar Mass (g/mol)86.2
Vapour Density (kg/m³) 25°C43.77
GWP1774
ODPNon-ozone depleting
REACHApproved
ATEL/ODL (kg/m³)0.29
Practical Limit (kg/m³) 0.31
Low Flammability LevelNon flammable
AIT (°C)704